1/03 UDC 6300 Process Controller Product Manual 121
4.13 Options Set Up Group, Continued
Table 4-12 Option Group Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
CUR OUT 2
(continued)
LSP 1
SETPOINT 1— Represents the value of local
setpoint#1 in units of PV for Loop 1.
IN ALG 1
INPUT ALGORITHM 1 OUTPUT — Represent the
output from input algorithm 1.
IN ALG 2
INPUT ALGORITHM 2 OUTPUT — Represent the
output from input algorithm 2.
PV LOOP2
PROCESS VARIABLE — Represents the value of
the Process Variable for Loop 2.
DEV LOOP2
DEVIATION 2 (PROCESS VARIABLE MINUS
SETPOINT) — Represents –100 to +100% of the
selected PV span in engineering units for Loop 2.
When Deviation is selected, only one operating
parameter will be entered. This value represents the
deviation level that will produce 20mA output. Zero
deviation will produce a center scale (12mA) output. A
negative deviation equal in magnitude to the 2nd current
output high value will produce a low end (4mA) output.
OUTPUT2
OUTPUT 2 — Represents the displayed controller
output in percent (%) for Loop 2.
SP LOOP 2
SETPOINT 2— Represents the value of the setpoint
in units of PV for Loop 2.
LSP LOOP2
LOCAL SETPOINT 2— Represents the value of
Local Setpoint#1 in units of PV for Loop 2.
4mA VAL
Low Scale Value
within the range of the
selected variable to
represent 4 mA
2ND CURRENT OUTPUT LOW SCALING
FACTOR — Use a value in engineering units to
represent all above except output.
Use value in percent (%) for Output. (Output can be
between –5 and +105%.)
20mA VAL*
High Scale Value
within the range of the
selected variable to
represent 20 mA
2ND CURRENT OUTPUT HIGH SCALING
FACTOR — Use a value in engineering units to
represent all above except output.
Use a value in percent (%) for Output. (Output can
be between –5 and +105%.)
*When Deviation is selected, only one operating
parameter will be entered. This value represents the
deviation level that will produce 20 mA output. Zero
deviation will produce a center scale (12 mA) output. A
negative deviation equal in magnitude to the Auxiliary
Output High Value will produce a low end (4 mA) output.
Table 4-12 continued on next page