182 UDC 6300 Process Controller Product Manual 1/03
5.13 Monitor 2 Loops of Control, Continued
Internal cascade
indication
When Internal Cascade has been configured, an “CAS” annunciator lights
as long as Loop 1 is operating in the remote setpoint mode (for example:
RSP is displayed).
If Local setpoint 1 and 2 is being used, the “CAS” will disappear until the
remote setpoint RSP CAS key is pushed to switch from local setpoint to
remote setpoint.
Switching between automatic and manual modes on either loop will not
affect the Internal Cascade indication.