162 UDC 6300 Process Controller Product Manual 1/03
5.7 Setpoints, Continued
Selecting the remote
setpoint source
You can select what you want your remote setpoint to be for each loop:
None
• Remote setpoint using input 2 toggled by the RSP/CAS key
• Remote setpoint using input 3 toggled by the RSP/CAS key
• Remote setpoint using input 4 toggled by the RSP/CAS
key
• Remote setpoint using input 5 toggled by the RSP/CAS
key
• Remote setpoint using Loop 1 Input Algorithm
• Remote setpoint using Loop 2 Input Algorithm
Use the procedure in Table 5-14 to select the remote setpoint source.
Table 5-14 Procedure for Selecting the Remote Setpoint Source
Step Operation Press Action
1
Select Set Up
Group
SET
UP
Until you see:
CONTROL
Lower Display
SET UP
Upper Display
or
CONTROL2
Lower Display
SET UP
Upper Display
for Loop 2
2
Select the
Remote
Setpoint
Source Prompt
FUNC
L1/L2
Until you see:
Lower Display
Upper Display
RSP SRC
The Remote Setpoint
source selection
NONE - not used
Input 2 - Input 2 as RSP
Input 3 - Input 3 as RSP
Input 4 - Input 4 as RSP
Input 5 - Input 5 as RSP
IN ALG1- Input algorithm 1
IN ALG2 - Input algorithm 2
3
Change
selection
or
to change the remote setpoint source.
ATTENTION
You cannot change the
Remote Setpoint Value using these
keys.
4
Return to
normal
operation
LOWR
DISP
This will return the controller to normal
operation.
Continued on next page