1/03 UDC 6300 Process Controller Product Manual 161
5.7 Setpoints, Continued
Switching between
local setpoint 3 and
local setpoints 1
or 2.
Use the procedure in Table 5-13 to switch between Local Setpoint 3 and
Local Setpoint 1 or 2.
Table 5-13 Procedure for Switching Between Local Setpoint 3 and
Local Setpoint 1 or 2
Step Operation Press Action
1
Select the
setpoint
RSP
CAS
to alternately switch between local
setpoint 3 and local setpoint 1 or local
setpoint 2 (when configured).
2
Change the
value
or
to change the local setpoint to the value
at which you want the process
maintained. The display "blinks" if you
attempt to enter setpoint values beyond
the high and low setpoint limits.
SP, SP2, or SP3 indicator will light to
match the lower display.
ATTENTION
"KEY ERROR" will
appear in the lower display if 3 local
setpoints are not configured or remote
setpoint is not configured.
Setpoint Ramp Rate will apply, if
enabled.
Continued on next page