3.9 Accutune Set Up Group
Introduction
The Accutune Set Up group offers these selections:
• (FUZZY) Fuzzy Overshoot Suppression - uses fuzzy logic to suppress
or eliminate any overshoot that may occur when the PV approaches
setpoint.
• (TUNE) Demand Tuning - The tuning process is initiated through the
operator interface keys or via a digital input (if configured). The algorithm
then calculates new tuning parameters and enters them in the tuning
group.
• (SP Only) SP Tuning -SP Tune continuously adjusts the PID
parameters in response to setpoint changes. You can select tuning on
minimum setpoint changes of 5% up to 15% span. Perform SP tuning after
you have configured the controller.
SP Tuning does not work with 3 Position Step Control algorithm.
• (TUNE + PV) or (SP + PV) PV Tuning - The (TUNE) Demand Tuning
or the (SP Only) Setpoint Tuning portions of these selections work as
stated above. PV Adapt will occur during Process Variable (PV)
disturbances (0.3% span or larger) which result from non-linearities,
process dynamics, load changes, or other operating conditions. When this
condition exists, the controller monitors the process response for 1 and 1/2
process cycles around the setpoint to determine whether there has been a
true process change or a momentary upset.